ALM-3276800002 Indicates that temperature exceeded the lower pre-alarm limit

Description

SRM/3/TEMPFALLINGALARM: OID [OID] temperature below minor threshold .(EntityPhysicalIndex=[INTEGER1], BaseThresholdEntry_entPhysicalIndex=[INTEGER2], BaseThresholdEntry_hwBaseThresholdType=[INTEGER3], BaseThresholdEntry_hwBaseThresholdIndex=[INTEGER4], BaseTrapSeverity=[INTEGER5], BaseTrapProbableCause=[INTEGER6], BaseTrapEventType=[INTEGER7], EntPhysicalName=[OCTET], BaseThresholdValue=[INTEGER8], BaseThresholdUnit=[INTEGER9], BaseThresholdLowCritical=[INTEGER10], BaseThresholdLowWarning=[INTEGER11])

This alarm was generated when the temperature was lower than the lower threshold.

Attribute

Alarm ID

Alarm Severity

Alarm Type

3276800002

Minor

Equipment alarm

Parameters

Name

Meaning

OID

Indicates the MIB object ID of the alarm.

EntityPhysicalIndex

Entity index.

BaseThresholdEntry_entPhysicalIndex

Index of the entity causing this temperature alarm.

BaseThresholdEntry_hwBaseThresholdType

Type of the detected entity (The value 1 indicates the temperature sensor of a certain type that is adopted by the S-switch.)

BaseThresholdEntry_hwBaseThresholdIndex

Index of the temperature sensor (The value begins from 1.)

BaseTrapSeverity

Severity code.

BaseTrapProbableCause

Error code.

BaseTrapEventType

Code of the event type.

EntPhysicalName

Entity name.

BaseThresholdValue

Current temperature.

BaseThresholdUnit

Unit of the temperature.

BaseThresholdLowCritical

Major lower threshold of the temperature.

BaseThresholdLowWarning

Lower threshold of the temperature.

Impact on the System

After the temperature exceeds the lower threshold, the device may fail to work normally. That is, packet loss may occur or even more seriously, the device may be suspended or abnormally reset.

Possible Causes

1. The lower threshold of the temperature was too high.

2. The ambient temperature was too low.

Procedure

  1. Run the display temperature { all | slot slot-id } command to check whether the ambient temperature is too low.

    • If so, increase the ambient temperature by turning up the air-conditioner.
    • If not, go to step 2.

  2. Run the display temperature { all | slot slot-id } command to check whether the set lower threshold of the temperature is too high.

    • If so, set the lower threshold of the temperature to a proper value. It is recommended that you run the undo temperature threshold unit unit-id command to restore the lower threshold to the default value.
    • If not, the alarm handling ends.