They include but are not limited to the following parameters. Configure parameters as required. The parameter marked with an asterisk (*) is mandatory.
Table 1 Description of device parameters

Attribute

Parameter

Description

Management Info

Parent Object

Name of the management domain to which the device belongs

Type

Type of the device

Name

Name of the device

The value is a string of 1 to 128 characters.

Med Node

Node ID used at the mediation layer

Protocol Type

Protocol version for the device

IP Address

It must be an IPv4 address in the X.X.X.X format, where X is a number ranging from 0 to 255. In addition, 0.0.0.0 is not allowed.

  • When the device protocol is MODBUS_TCP, set the IP address of the data collector to which the device connects.
  • When the device protocol is MODBUS_RTU, set the IP address of the data collector to which the device connects.
  • When the device protocol is Simple Network Management Protocol (SNMP), set the IP address of the device.
  • When the device protocol is CInterface, set the IP address of the device.

Port

The value is an integer ranging from 0 to 65,535.
  • When the device protocol is MODBUS_TCP, set the corresponding port of the device. The port is 502 by default.
  • When the device protocol is MODBUS_RTU, set the port number of the data collector to which the device connect.
  • When the device protocol is SNMP, set the corresponding port of the device. The port is 161 by default.
  • When the device protocol is CInterface, set the corresponding port of the device.

Device Address

The value is an integer ranging from 0 to 255.

  • When the device protocol is MODBUS_TCP or MODBUS_RTU, set the address of the device.
  • When the device protocol is SNMP, the device address parameter does not exist.
  • When the device protocol is CInterface, the device address parameter does not exist.
NOTE:

The value combination of the IP Address, Port, and Device Address must be unique to each device.

Out Time

Time when testing the connection times out. The default value is three seconds.

The value is an integer ranging from 1 to 60.

NOTE:
  • When the NMS delivers a heartbeat message to the device, the device determines that the device does not respond if the duration exceeds the value of this parameter.
  • This parameter affects the detection speed when the device is disconnected. The heartbeat is invalid only when the time specified in Out Time is reached. In this case, the device may be disconnected.
  • This parameter affects the packet response success rate of the device. If the device takes 2 seconds to respond to the NMS and Out Time is set to less than 2 seconds, the device does not receive any response.

Security Name

Name of a user
NOTE:

Specify this parameter when configuring devices that support the SNMPv3 protocol.

Context Name

Context name of the managed object

The value is a string of 0–60 characters and cannot contain special characters .

Authentication Protocol

Set this parameter to the value of Authentication Protocol configured on the device. The default value is SHA.

The SHA and MD5 protocols are supported.

NOTE:

Specify this parameter when configuring devices that support the SNMPv3 protocol.

NOTICE:

MD5 is an insecure protocol. SHA is recommended.

Authentication Password

Set this parameter to the authentication password configured on the device.

Value range: a–z, A–Z, 0–9, _ (8–15 characters, at least two types of characters, different from the user name or its reverse)

NOTE:

Specify this parameter when configuring devices that support the SNMPv3 protocol.

You are advised to set Authentication Password and Privacy Password to different values.

Privacy Protocol

Set this parameter to the value of Privacy Protocol configured on the device. The default value is AES128.

The AES128 and CBC_DES protocols are supported.

NOTE:

Specify this parameter when configuring devices that support the SNMPv3 protocol.

NOTICE:

DES is an insecure protocol. AES is recommended.

Privacy Password

Set this parameter to the proprietary protocol key configured on the device.

Value range: a–z, A–Z, 0–9, _ (8–15 characters, at least two types of characters, different from the user name or its reverse)

NOTE:

Specify this parameter when configuring devices that support the SNMPv3 protocol.

You are advised to set Authentication Password and Privacy Password to different values.

Context Engine ID

Context engine ID of the managed object

The value is a string of 0–60 characters and cannot contain special characters .

Read Community

Set this parameter to the read community configured on the device.

Modifying the community per three months is advised.

NOTE:

Specify this parameter when configuring devices that support the SNMPv1/v2 protocol.

Write Community

Set the write community configured on the device.

Modifying the community per three months is advised.

NOTE:

Specify this parameter when configuring devices that support the SNMPv1/v2 protocol.

Connection Mode

Connection mode of a device. You can set this parameter to Non-SSL Connection or SSL Connection.

If you modify the connection mode on the NMS, you must modify the connection mode on the device WebUI accordingly.

NOTE:
  • The connection mode settings for the NMS and device must be the same.
  • By default, Connection Mode is set to SSL Connection for the NMS and device.

Authentication Password

Re-authentication password for the NMS and device

  1. Click Modify.
  2. In the displayed dialog box, enter New Password and Confirm Password.
    NOTE:
    • The password must contain 8 to 32 characters.
    • The password includes at least three of the following types: lowercase letters, uppercase letters, digits, and special characters (~!@#^*_={}:,./?-`$). If the password does not comply with the rules, please change the password on the device side.

    Change the password periodically (every three or six months) to improve system security and prevent security risks, such as violent password cracking.

  3. Select a value for Send To Device.
    NOTE:

    If you select YES, the re-authentication password for the NMS and device is changed at the same time. If you select NO, only the re-authentication password for the NMS is changed.

  4. Click OK.
NOTE:

You can only change the re-authentication password for the ECC800-Pro.

Camera Code

The camera code specified in the intelligent video surveillance system contains 15 digits. For details, see Device Installation and Commissioning Guide.

NOTE:

The camera code is the value of Device ID whose last three digits are replaced with 101. For example, if the value of Device ID is 878719000000000, the value of Camera Code is 878719000000101.

Bind AccessController

AccessController

When creating a fingerprint controller, you can set whether to bind the fingerprint controller to the corresponding access controller.

NOTE:
  • The fingerprint controller must be bound to the TycoSun access controller for use.
  • The access controller to be bound must be in single-card mode.

Door Passage

When creating a TycoSun access controller, Door Passage is Enabled by default. You can set Door Passage to Enabled or Disabled as required.

NOTE:

When creating a fingerprint controller, if a door passage whose status is Enabled, the fingerprint controller can bind the door passage.

Setting UPS

UPS

When creating an iBOX, you can set whether to bind UPSs in the same management domain.

Electricity Info

Rated Power (kW)

Rated power consumption of a device

The value is a floating number ranging from 0 to 65,535 (three decimal places).

Power Mode

Click , and choose Single power supply or Dual power supply.

Asset Info

Model

Model of the device.

The value is a string of 0 to 64 characters.

Manufacturer

Manufacturer of the device

The value is a string of 0 to 64 characters.

Serial Number

Serial number of the device upon delivery

The value is a string of 0 to 64 characters.

Lock Number

The value of this parameter cannot be modified.

Weight (kg)

Weight of the device

SN

Device number

The value is a string of 0 to 64 characters.

Location

Location of the device in the management domain

The value is a string of 0 to 64 characters.

Airflow Type

Select Front to Rear, Bottom to Top, Side Left to Side Right, Side Right to Side Left, or Front to Top.

Status

Device status Select Enabled, Power-on, Power-off, Idle, or Offline.

Project No.

The value is a string of 0 to 64 characters.

Start Date of Use (yyyy-MM-dd)

Device activation time

TemperatureRange (°C)

Temperature range in which the device works properly

The value can be modified.

Owner

The value is a string of 0 to 64 characters.

Department

The value is a string of 0 to 64 characters.

InstallationMode

The installation modes of different devices are different. Select the installation mode as required.

Select Floor Build In, Cabinet Build In, Wall Build In, or Ceiling installation. The cabinet and PDU also support installation modes of Antistatic floor installation and Cement floor installation.

Wire Type

Select Ascending Line, Down Line, or Floor Line.

Status Info

Start Date Of Use (yyyy-MM-dd)

Start date of use of the device

Last Maintenance (yyyy-MM-dd)

Last maintenance time of the device

Extended Info

Rated Output Power (kW)

Rated output power of the device

The value is an integer ranging from 0 to 65,535.

Rated Cooling Capacity (kW)

Rated cooling capacity of the device

Distribution Area

Select Inlet Side or Outlet Side.

Install Height (m)

Select 0.6, 1.2, or 1.8.

TemperatureRange (°C)

Temperature range in which the device works properly

The value can be modified.

InstallationMode

The installation modes of different devices are different. Select the installation mode as required.

Select Floor Build In, Cabinet Build In, Wall Build In, or Ceiling installation. The cabinet and PDU also support installation modes of Antistatic floor installation and Cement floor installation.

Protocol Info

Number of Heartbeats

Indicates that the device is disconnected for N consecutive heartbeat failures. The default value is 3.

The value is an integer ranging from 1 to 3.

NOTE:

This parameter affects the speed at which the NMS detects device disconnection.

Heartbeat Period (s)

Interval for the NMS to send heartbeat detection messages to the device to determine whether the device is connected.

The value is an integer ranging from 1 to 10,000.

NOTE:

The default value varies according to protocols.

Sending Interval (ms)

Interval at which the device sends each packet. The default value is 600 ms.

The value is an integer ranging from 50 to 10,000.

NOTE:

This parameter affects the packet processing efficiency. Based on the response efficiency of the device, the device can process a packet within the interval specified by Sending Interval (ms), which is the highest efficiency.

Receiving Timeout (ms)

Indicates the timeout period for the NMS to receive packets from the device. The default value is 1000 ms.

The value is an integer ranging from 500 to 10,000.