ALM-3276800322 The Power Module Is Removed
Description
ENTITYTRAP/4/POWERREMOVE: OID [OID] Power has been removed.(Index=[INTEGER], EntityPhysicalIndex=[INTEGER], PhysicalName="[OCTET]", EntityTrapFaultID=[INTEGER])
The power supply unit was removed.
Attribute
Alarm ID |
OID |
Alarm Severity |
Alarm Type |
---|---|---|---|
3276800322 |
1.3.6.1.4.1.2011.5.25.219.2.5.1 |
Warning |
Equipment alarm |
Parameters
Name |
Meaning |
---|---|
OID |
Indicates the MIB object ID of the alarm. |
Index |
Indicates the index. |
EntityPhysicalIndex |
Indicates the physical entity index. |
PhysicalName |
Indicates the physical entity name. |
EntityTrapFaultID |
Indicates the error code. |
Impact on the System
Boards cannot be powered on because power is insufficient.
Possible Causes
The power supply unit was removed.
Procedure
- Check whether the power supply unit was removed manually.
- If so, no action is required.
- If not, reinstall the power supply unit and go to step 2.
- Run the display power command to check whether the power supply unit is present.
- If so, replace the power supply unit.
- If not, go to step 4.
- End.
- Collect alarm information and configuration information, and then contact technical support personnel.
Related Information
None